Conduit fill
40% allowed · NEC Ch. 9, Table 1
CONDUIT PULL CHECKER
Check conduit fill and ampacity derating together.
This pull meets the checked fill and ampacity limits.
40% allowed · NEC Ch. 9, Table 1
310.15(C)(1) + Table 310.16
Fill, derating, and terminations work together here. Ordinary small-wire protection: 30 A max.
A field check, not an inspection guarantee. Verify the adopted NEC edition, equipment listings, breaker selection, and local requirements with your AHJ.
Fill: 0.1477 in² ÷ 0.864 in² = 17.09%. Allowed area: 0.346 in². Verdict uses unrounded areas.
#10 AWG: 40 A × 80% conductor adjustment × 100% ambient correction = 32 A. Capped at 35 A for 75°C terminations → 32 A.
Required: 30 A × 100% noncontinuous = 30 A. Every circuit group is checked against this load.
The rules behind your result, in one place.
Explore the changes that make a difference.
BEFORE THE WIRE GOES IN
PassPull checks how much space your conductors occupy, how conductor count and ambient temperature affect ampacity, and where equipment termination ratings limit the result. Use one NEC 2023 setup for all three checks.
Choose EMT, PVC Schedule 40, RMC or IMC; enter every conductor, the current-carrying count, termination rating and required load; then check the result. See the supported sizes and assumptions before relying on a setup.
Space in the pipe and allowable current are different limits. Check both before deciding that a pull works.
Read the guideThe number used for heat adjustment is often different from the number used for physical fill.
Read the guideThe wire jacket and the equipment connections place different limits on a circuit.
Read the guideIt means your inputs meet the implemented checks within the supported scope. It does not evaluate the entire installation or replace your adopted NEC, equipment listings, and local inspector’s requirements.
It can reduce the fill percentage. The same current-carrying count still receives the same adjustment factor. Try a suitable larger circuit conductor, or plan separate raceways for complete circuits and recheck each one.
No. Save up to 20 named pulls in this browser, copy a setup link, or download a field-check record. Local saves do not sync between devices. A shared setup must be checked again by its recipient.
PASSPULL — PASS (checked limits only) 1 in. EMT · NEC 2023 6 × #10 AWG copper THHN/THWN-2 · circuit 1 × #10 AWG copper THHN/THWN-2 · ground Current-carrying: 6 · Termination: 75°C · Ambient: 30°C Fill: 17.09%; allowed 40% (0.1477 / 0.346 in² allowed). Lowest allowable ampacity: 32 A. Required: 30 A (noncontinuous). Small-conductor protection cap: 30 A. Final breaker selection not evaluated. #10: 40 A × 0.8 × 1 = 32 A, terminal limit 35 A → 32 A. PASSPULL · NEC 2023 Conduit fill: Chapter 9, Table 1 (including Notes 3, 6 and 7), Table 4, Table 5. Conductor adjustment: 310.15(C)(1). Ambient correction: Table 310.15(B)(1)(1). Base ampacity: Table 310.16. Terminations: 110.14(C). Small-conductor overcurrent protection: 240.4(D). Continuous load sizing: 210.19(A)(1) / 215.2(A)(1), as applicable. Field check only; verify adopted code, equipment ratings and AHJ requirements. Not evaluated: voltage drop, ground sizing, bonding, box fill, bends/pulling tension, special circuits, rooftop adders, final breaker selection. Verify before installation.